Evaluation of an Infra-Red
Two-Stage
Heating System in a Commercial Application
R.D. MacDonald, P.Eng., Member AHSRAE M.E. Armstrong, P.Eng.,
K.G. Boyd, P.Eng
Appreciation for technical support and funding from Union Gas, Chatham,
ON and
Brant Radiant Heaters Ltd., Paris, ON, is gratefully acknowledged.
ASHRAE Research Project Number: 4643 |
Download Summary Printed by
Detroit Radiant Products Co.
|
 |
 |
|
INFRARED HEATING SYSTEM |
FORCED AIR HEATING SYSTEM |
OBJECTIVE:
- To determine effectiveness (fuel utilization and comfort) of a
two-stage heating system designed to provide space heating and
offset elevated losses from overhead door usage.
- To determine how a two-stage heat system better meets heat
requirements vs. forced air heat system.
|
 |
|
IR vs. FA Temperature Cycling |
SITE DESCRIPTIONS:
Commercial facility with frequent overhead door opening facilitating the
movement of supplies.
Installed a forced-air unit heater (FA) and a tube-type infrared heater (IR)
that operate by a common thermostat with a manual override switch to allow
either FA or IR operation.

PROCEDURES & METHODS:
- Measure temperatures at 10 minute intervals,
outside and a variety of inside and slab locations.
- Measure gas usage daily at designated times,
conduct regular interview with staff on comfort.
- Predetermined operating cycles for FA and IR
heater (i.e. alternate weeks, etc.).
RESULTS:
Test 1
October 1, 1999 - February
17, 2000. Target set point was 17șC
- To establish a test methodology using the
systems and verifying the controls.
- Systems operated during the heating season at
1-2 week alternating equal intervals, FA then IR.
- Energy savings comparing FA and IR proved
minimal
Test
2
February 18 - April 28,
2000. Target set point for IR 16șC and FA 19șC.
(Actual average 13.2șC IR
and 17.7șC FA)
- Systems operated during the heating season at
1 week alternating intervals.
- IR savings measured 19.5%, savings influenced
by the lower set point of IR.
Test
3
October 16, 2000 - April 12,
2001. Target set point for IR 14șC and FA 17șC.
(Actual average 21.2șC IR
and 18.9șC FA)
- Systems operated during the heating season at
1 week alternating intervals.
- IR savings measured 23%, (note: average
temperature higher for IR).
Test
4
December 15 - March 25,
2000-2001 and 2001-2002. Target set point for IR 17șC.
(Actual delta T inside to
outside for two time periods was 21.3șC IR and 21.8șC)
- IR and FA systems cycled weekly 2000-2001.
- IR only 2001-2002.
- Saved 25.4%with continuous infrared vs.
weekly interval IR and FA.
|
 |
|
Slab Temperature Changes of FA and IR |
|
 |
|
Average IR Low / High Fire vs. FA Opening Time |
|
 |
|
IR Total On-Time vs. High Fire |
CONCLUSION:
- IR heating saved up to 23% over a
conventional FA heating system.
- The thermal flywheel effect in the slab
contributes to energy use efficiency.
- A weekly cycle of FA vs. IR is not a useful
method of evaluating potential in either system due to the flywheel
effect.
- Two stage infrared heat system ran on low
fire longer than FA per on-cycle; plus only used high fire 8-23% of
the total on-time for heating.
|
 |
|
FA vs. IR Energy Usage |
|
 |
|
Alternating IR vs. Continuous
Energy Usage |